BMS Main 3 / BMS Main 3X

Controller / Strings controller

Modular BMS controller for 24-2000V batteries

Depending on firmware, device can act as a battery controller (BMS Main 3) that interacts with measuring modules, or as a controller of parallel batteries (BMS Main 3X).

BMS Main 3 can control up to 40 measuring modules and manage a battery consisting of 720 cells.

BMS Main 3X controls up to 32 batteries connected in parallel, each of them is managed by the BMS Main 3.

BMS Main 3 / BMS Main 3X

image

  • 6 switches for contactors
  • 8 discrete inputs
  • 4 discrete outputs

image

  • SOC, DOD, SOH estimation
  • Cycles, energy counting

image

  • 3xCAN, RS-485, USB
  • Wi-Fi, LAN, GSM (over an extension modules)

image

  • SD-card logging

Links

Documentation for BMS Main 3

Documentation for BMS Main 3X

Firmware for BMS Main 3

Firmware for BMS Main 3X

Downloads

ElectricDeviceMonitor

Compatible controllers (for BMS Main 3X only): BMS Main 3

Compatible measuring modules (for BMS Main 3 only): BMS Logic 12S, BMS Logic 12, BMS Logic 18, BMS Logic 2.0

Compatible displays (for BMS Main 3X only): BMS Display

Compatible displays (for BMS Main 3 only): BMS Display, BMS Indication

Compatible additional modules: BMS IMD, BMS Wi-Fi, BMS LANmodule, BMS GSM

ParameterValue
Supply voltage, V 9 to 32
Current consumption @24 V, mA (max) 150
KEYRUN or CHARGE_ON signal for powering on the device, V, (minimum) 8.5
Number of BMS Logic devices (relevant for BMS Main 3) 1 to 40
Number of cells (maximum) (relevant for BMS Main 3) 720
Number of parallel batteries (relevant for BMS Main 3X) 1 to 32
Number of programmable switches for contactors (9-32V, 2.5A) 6
Number of programmable discrete inputs (dry contact) 6
Number of programmable discrete inputs 9-32V 2
Number of programmable discrete outputs (open drain, 40V, 1A) 4
Number of connected current sensors (two signal lines for each sensor) 3
Error in measuring signals from current sensors, V, max ± 0.001
Current sensor types Hall-Effect sensor, bidirectional (LEM series: HASS, HTFS, DHAB or analogues)
Number of HV measurement inputs (two signal lines on each input) 2
High voltage measurement range, V 10 ÷ 1000
High voltage measurement error, V, max ± 2
Number of connected external temperature sensors (100 kOhm NTC-thermistors) 2
Temperature measurement error using external temperature sensors, ºС, max ± 2
Temperature measurement error using a built-in temperature sensor, ºС, max ± 2
Humidity measurement error using a built-in humidity sensor, %, max ± 10
Current in the HVIL, mA, typical 25
Total resistance in the HVIL, Ohm, max 200
Number of USB interfaces 1
USB speed, Mbit/s 12
Number of CAN interfaces 3
CAN speed, kbps 125, 250 (default), 500, 1000
Number of RS-485 interfaces 2
RS-485 bus speed, bps 600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
Output voltage of CAN2 power supply, V 5 ± 0.5
Output current of CAN2 power supply, mA, max 400
Rated insulation voltage, AC 50Hz, 1 minute, VRMS (minimum): 1) Between CAN1, RS-485-1, discrete inputs/outputs and power lines, 2) Between CAN1, RS-485-1, discrete inputs/outputs and HV measurement lines, 3) Between power lines and HV measurement lines 3500
Dimensions (length × width × height), mm 200 × 120 × 12
Weight, g 150 ± 10
Operating temperature range, °С -40 ÷ 85
The degree of protection from external influences IP00

BMS Main 3 / BMS Main 3X can be configured using the ElectricDeviceMonitor over USB, CAN or a TCP network (in this case, the BMS Wi-Fi or BMS LANmodule must be installed).